Chapter IV Function Parameter Table
90
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
compensation, the output frequency of the
drive is automatically adjusted according
to the load torque of the motor, which can
reduce the speed change of the motor
caused by load changes, as shown in the
figure.
2. Electric status: When the actual speed
is lower than the input speed, gradually
increase the compensation gain (FC.04).
3. Generation status: When the actual
speed is higher than the input speed,
gradually increase the compensation gain
(FC.04).
4. The filter time constant of slip
compensation. The shorter the filter time,
the faster the response, but too short will
easily cause oscillation and speed
instability.
FC.05
Slip
compensat
ion filter
time
0.1ms
10.0ms
○
FC.06
Cooling
fan control
0: Run in automatic mode
Note: The fan is turned off at least 3
minutes after stop and when the
temperature is lower than 40 degrees.
1: The fan keeps rotating during power-on
1
0
×
FC.07
Accelerati
on/deceler
ation time
unit
0: Second
1: Minute
1
0
×
FC.08
Droop
control
frequency
Set range: 0.00
~
10.00Hz
1. The droop control is suitable for the
occasions where multiple drives drive the
same load. By setting this function,
multiple drives can reach a uniform
distribution of power when driving the
same load. Transmission gears are shown
in the following figure (5 drives drive the
conveyors of 5 motors)
0.01Hz
0.00Hz
○