Chapter IV Function Parameter Table
78
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
F8.35
Water
supply
absolute
sleep
detection
time
Setting range: 0~3600.0s
When the drive sleeps and decelerates to
the lower limit frequency, it will run at
the lower limit frequency for the time
defined by F8.35 and then go to zero
frequency operation.
0.1s
10.0s
○
F8.36
Delay time
of pump
reduction
in
shutdown
Set range
:
2~240s
This function code is used as the delay
time between successive shutdown of
water pumps in power frequency
operation when manual shutdown is
carried out in automatic control mode.
1s
2s
○
F8.37
Add and
reduce
pump
delay time
Set range
:
1~36s
The function code is used to judge the
delay time before adding and reducing the
pump.
1s
5s
○
F8.38
Add pump
action
frequency
Set range
:
Lower limit frequency
~
Upper
limit frequency
When the drive is in the running
condition, the pump frequency value
≥F8.38 set value, and after F8.37 delay
time, the number of pumps will be
increased.
0.01Hz
50.00Hz
×
F8.39
Reduce
pump
operation
frequency
Set range
:
Lower limit frequency
~
Upper
limit frequency
When the drive is in the running
condition, the pump frequency value ≤
F8.39 set value, and after F8.37 delay
time, the number of pumps will be
reduced.
0.01Hz
15.00Hz
×
Group F9: Multistage speed control parameters
F9.00
Simple
PLC run
mode
selection
LED single digit: PLC run mode
0: No action
1: Stop after a single cycle: The drive will
stop automatically after completing one
cycle. You need to give a run command
again to start.
2: Keep the final value after a single
cycle: The drive will automatically keep
the operation frequency and direction of
the last stage after completing one cycle.
1111