Chapter IV Function Parameter Table
36
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
F8.15
5.0%
FC.17
14
F0.05
Function
code
operation
password
Setting range: 0~65535
0 indicates no password, set any non-zero
number, the password protection function
will take effect immediately, please keep
the set password in mind.
After setting the password, if you want to
clear the password, you must enter the
correct password first, and then set the
password value to 0.
After setting the password, if you want to
change the password, you must clear the
password before you can set a new
password.
Note: The password protection
authority is set in F0.00, which is used
to prohibit unauthorized personnel
from viewing and changing the
function code parameters.
1
0
○
F1 group :Basic operating parameters
F1.00
Control
method
0: Reserved
1: V/F control: Sound versatility, and
stable operation, can effectively improve
low-frequency torque and suppress
current oscillation, with slip
compensation and automatic voltage
adjustment functions, further improving
control accuracy.
1
1
×
F1.01
Run
command
channel
selection
0: Keypad run command channel: By the
RUN key, and the STOP key, you can
control the drive to run and stop, press
and hold the ▲ key and the ▼ key in the
“
JOG-
” interface, you can perform
forward jog and reverse jog.
1: Terminal run command channel:
Control the running and stopping of the
drive through the multifunctional input
terminal forward, reverse, forward jog,
reverse jog, etc. (The corresponding
multifunctional input terminal’s function
must be defined by the F6 and Fd
parameter groups).
2: Serial port run command channel:
Control the running and stopping of the
drive through communication.
1
0
○