Chapter V Basic Operation Instructions
155
0x04
0x03
0x1000
0x0001
None
0x809F
0x04
0x03
None
0x02
0x1388
0x7912
Write the acceleration time 1 (i.e. function code F1.11) of 5# drive to 1.00s, and do not save
after power failure.
Address
Function code
Register
address
Register content
Verification
code
0x05
0x06
0x010B
0x0064
0xF99B
0x05
0x06
0x010B
0x0064
0XF99B
Read the output current of 5# drive, and the drive response output current is 3.00A.
Address
Function code
Register
address
Register number or
read bytes
Register
content
Verification
code
0x05
0x03
0x1002
0x0001
None
0x208E
0x05
0x03
None
0x02
0x012C
0x49C9
Calibration relationship of the drive
A) The calibration of the frequency is 1:100
To make the drive run at 50Hz, the main setting shall be 0x1388 (5000).
B) The calibration of the time is 1:100
To make the drive acceleration time be 3s, the function code setting shall be 0x012C (300).
C) The calibration of the current is 1:100
If the drive feedback current is 0x012C (300), the current of the drive is 3A.