Chapter IV Function Parameter Table
65
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
mode
selection
(DI5)
F6.20
HDO
terminal
output
mode
selection
(DO2)
0: Switch output
1: High-frequency pulse output (see
F5.27
~
F5.30)
1
0
×
F6.21
Reserved -
-
-
*
F6.22
Counter
reset value
setting (set
count
value
arrival)
F6.22 set range: F6.23
~
9999
F6.23 set range: 0
~
F6.22
F6.22 and F6.23 are supplementary
definitions for No. 13 and No. 14
functions in the terminal output function.
1. The set count value input refers to the
number of input pulses from DIx (count
trigger signal input function terminal),
before the DOx (open collector output
terminal) or the relay outputs an
indication signal. As shown in the figure,
when DIx inputs the 8th pulse, DO1
outputs an indication signal, and F6.22 =
8 in this case.
2. The specified count value input refers
to the number of input pulses from DIx,
before the DOx or the relay outputs an
indication signal, till the set count value is
reached. As shown in the figure, when
DIx inputs the 5th pulse, DO2 outputs an
indication signal, till the set count value 8
is reached, in this case F6.23 = 5.
3. When the specified count value is
greater than the set count value, the
specified count value is invalid.
1
0
○
F6.23
Counter
detection
value
setting
(specified
count
value
arrival)
1
0
○
F6.24
DI polarity
switch 1
00000~11111
LED single digit: DI1 polarity
LED tenth digit: DI2 polarity
LED hundredth digit: DI3 polarity
LED thousandth digit: DI4 polarity
LED 10 thousandth digit: DI5 polarity
This function code is used to set the
polarity of the digital input. When the bit
is set to 1, the input polarity is positive
(connected to the common terminal is
valid and disconnected is invalid). When
the bit is set to 0, the input polarity is
11111
11111
○