Chapter IV Function Parameter Table
44
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
set in F2.04 for DC braking and
then start from the start
frequency.
2: Speed tracking and restart:
Track the current speed and
direction of the motor, and
perform smooth start without
impact on the motor that is still
rotating.
LED tens digit: Speed tracking mode
0: Track down from the frequency of
shutdown, usually this method is
used.
1: Track down from the maximum
frequency, suitable for power
generation load.
F2.01
Start
frequency
F2.01 set range: 0.20
~
60.00Hz
F2.02 set range: 0.0
~
10.0s
1. The start frequency refers to the initial
frequency of the drive at start. As shown
in fs in the figure, setting a proper start
frequency can increase the torque at start.
2. Within the hold time of the start
frequency, as shown as t1 in the figure,
the output frequency of the drive is the
start frequency, and then operate from the
start frequency to the target frequency.
3. The start frequency value is not limited
by the lower frequency limit.
0.01Hz
0.50Hz
○
F2.02
Start
frequency
hold time
0.1s
0.0s
○
F2.03
Start DC
braking
current
F2.03 set range: 0.0
~
150.0% drive rated
current
F2.04 set range: 0.0
~
30.0S (0.0 indicates
the DC braking is not active)
0.1%
100.0%
○