Chapter V Basic Operation Instructions
103
5.1.3 Terminal two-wire start protection and start logic block diagram
The terminal two-wire start protection start can realize that the drive automatically starts when
the drive is powered on, the fault is cleared, or the command channel is switched to the terminal
two-wire mode, if the terminal run command is valid.
For safety's sake, use this function with caution, otherwise, it may cause personal injuries
and property losses.
Related parameter table:
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value Change
F1.01
Run
command
channel
selection
0: Keypad run command channel
1: Terminal run command channel
2: Serial port run command channel
1
0
○
F1.24
Running
direction
setting
0: Forward
1: Reverse
1
0
○
F2.06
Start
protection
selection
(only valid
for two-wire
control)
This function realizes whether the drive
automatically starts running when the drive
is powered on, the fault is cleared, or the
command channel is switched to the
terminal two-wire mode.
0: If the run command is valid, the drive
does start, and the drive is in the running
1
0
×