Page | 17
Change Inputs
By default, all inputs are pre-set as ‘
unused
’ so you will need to program each individual input
you require. The input will not be ‘live’ (and hence cannot be walk tested) until you have
exited the Engineer Menu (please see Page: 5)
4.1.8 Input Types
Number & Type
Operation
00 Unused
Factory default.
Input is programmed out of operation.
01 Fire
Active at all times.
Audible response: Full (differentiated).
Communicator: ‘Fire’ signal
02 Gas
Active at all times.
Audible response: Full (differentiated)
Communicator: ‘Gas’ signal
03 HU
Active at all times.
Audible Response: Full (differentiated)
Communicator: ‘Hold Up’ and ‘Input HU’ signals
04 Silent
HU
Active at all times.
Audible Response: None
Communicator: ‘Hold Up’ and ‘Input HU’ signals
05 Tamper
When unset:
Audible Response: Internal only
Communicator: ‘Tamper’ signal.
When set:
Audible Response: Full
(differentiated). Communicator: ‘Tamper’
06 Intruder
Active when set.
Audible Response: Full
Communicator: ‘Intruder’ and ‘Unconfirmed’ signals
07
Final Exit
(FX) (see
type: 43
Final Exit 2)
Active when set
– initiates entry timer, if system not unset before entry
time expires: Audible Response: Full. Communicator: ‘Intruder’ and
‘Unconfirmed’ signals
08
Entry Route
(ER)
Active when set
, except during entry time.
Audible Response: Full. Communicator: ‘Intruder’ and ‘Unconfirmed’
signals
09 ER
(Area FX)
(For use with level sets).
When fully set, acts as Entry route input, as
above. When part set, acts as Final Exit input, as above.
10
FX
(Area ER)
(For use with level sets).
When fully set, acts as Final Exit input, as
above. When part set, acts as Entry route input, as above.
11 PTS
Active during exit time
to complete Setting procedure
No audible or communicator response.
Note: May be used to act as ‘doorbell’ by use of ‘chime’ attribute.
12 Switcher
Active at all times.
No audible or communicator response
Triggers associated output or switches other equipment
13 Day
Alarm
When set:
Audible Response: Full. Communicator: ‘Intruder’ and
‘Unconfirmed’ signals.
When unset:
Audible Response: Programmable.
Communicator: ‘Day Alarm’ signal
15 Ward
Control
Input is allocated by system software and cannot be reprogrammed to a
different type, though relevant attributes may be adjusted.
16 Fault
Active when unset.
Audible Response: Graduated internally
Triggers ‘Global Fault 1’ outputs if the system is set.
Triggers ‘Global Fault 2’ output if the system is set/unset.
17 Closure
Supervision
Active during Setting procedure.
No audible or communicator
response. Prevents system being set whilst active
18 Shunt
Input
Active at all times.
No audible or communicator response
Accepts input from keyswitch (or equivalent) to shunt the inputs
assigned to it. Associated outputs are available.
After 10 seconds the
detectors in the shunt list will be active. See page: 21
19 Unset
Input Active when set.
Accepts input from keyswitch (or equivalent) to Unset
the Area/Level set assigned to it.