Page | 10
Inhibit Fire/HU
This function allows you to select if you would like the EURO system to respond to or inhibit
Fire
and
Hold-Up
Alarms whilst in the Engineers Menu.
Using the
and
keys, scroll to
‘
INHIBIT FIRE/HU?
’
Press the
key
The following will be displayed:
Enter
: for No
(Default)
Enter
: for Yes
Press the
key
You will be returned to the Engineer
Menu.
Software Revision
This option identifies the software version number, software serial number and product.
Using the
and
keys, scroll to
‘
SOFTWARE REVISION?
’
Press the
key.
The version number will be displayed.
Press the
key. You will be returned
to the Engineer Menu.
Choose Mode
4.1.1 The End of Line Range
This programs the panel to operate with different resistor values:
1K
=
Alarm: 1K
,
Tamper: 1K.
2K2
=
Alarm: 4K7, Tamper: 2K2.
(Default)
4K7
=
Alarm: 4K7, Tamper: 4K7.
4.1.2 SR or DR
This programs whether the whole alarm panel and any ZEMs will be used in Singe End of Line
mode (SR) or Double End of Line (DR) resistor mode.
(DR is selected as default)
4.1.3 Input Response Time
This selects the time that an input trigger must be present before the whole system responds
by generating an alarm, and is programmable from 100mS (0.1 seconds) to 3000mS (3
seconds).
Note: Settings below 400ms do not comply with PD6662/EN50131.
400ms is
selected as default.