Page 28
Operations Manual SC-610
Harmonic Drive AG
900105
11/2005
4.2.7 Interface Cables
The bit-rate for communication is 57600 baud (factory preset). Other bit-rates are possible. To prevent
interference it is advised to keep cable length at 3m or less. Shielding interface cables is highly
recommended. It is also advised not to run the interface cable next to high power or AC signals such as
servo amplifiers, line voltages etc.
The wiring from PC to drive connector X6 for serial interface must be as shown below:
A) RS232
RS232 is the standard interface.
CAUTION
:
The serial connector on the SC610 (X6) can be configured as either
RS232 or RS422 / RS485. Pin 9 is used to carry +8V for powering
certain keypad peripherals. Ensure that pin 9 is not connected to
ground or to equipment that could be damaged by the +8V supply
B) RS485
The RS485 is an optional interface only and must be adjusted via DIP switch AS1.10. For further information
concerning multi-drop applications please refer to appendix D.
TX-
TX+
RX+
RX-
DGND
3
7
8
2
5
6
7
8
9
TX+
TX-
RX-
RX+
DGND
1)
Drive
9 pol. SUB-D
FEMALE
Master
1) Wiring principle at the master may be different than shown above. Please refer to the interface
description of your master system.
Summary of Contents for SC-610 Series
Page 1: ...Operations Manual AC Servo Controller SC 610 No 900105 11 2005 24 11 2005 FA...
Page 3: ......
Page 52: ...Operations Manual SC 610 Page A1 Harmonic Drive AG 900105 11 2005 APPENDIX...
Page 64: ...Operations Manual SC 610 Page A13 Harmonic Drive AG 900105 11 2005 APPENDIX G...
Page 65: ...Page A14 Operations Manual SC 610 Harmonic Drive AG 900105 11 2005 APPENDIX H...
Page 66: ...Operations Manual SC 610 Page A15 Harmonic Drive AG 900105 11 2005 APPENDIX I...
Page 67: ...Page A16 Operations Manual SC 610 Harmonic Drive AG 900105 11 2005 APPENDIX J...
Page 68: ...Operations Manual SC 610 Page A17 Harmonic Drive AG 900105 11 2005 APPENDIX K...
Page 69: ......