87
CONTROLLER FUNCTIONS & MODES
13. CONTROLLER FUNCTIONS & MODES
Function/Mode
Control
Cleaning
Edit
Calibration
Manual
Error
Ru
n
Start up
Hold
Alarm
Activated by
Start-up T
imeout/
End of Alarm_Hold_
Cleaning_Edit_Calibration_
Manual Mode
Power On
External Input/
Soft Key (Manual Hold)/
Alarm Condition/Cleaning_
Edit_Calibration_Manual
Mode
Parameters alarms, control
setpoints overtime, probe
disconnected
Timer/Schedule/Ext. Input/Soft Key
(Manual Start)
Soft key
Soft key
Soft key
Hardware error
Ended by
Alarm & Error Conditions/
Hold_Cleaning_Calibration_
Manual Mode Requests
Timeout
Hold conditions no longer
present
Alarm condition no longer
present
Complete cleaning cycle/
Soft Key (Manual Stop)/
Hold Mode_Edit Mode_Manual
Mode request
Soft key /
Timeout
Soft key / T
imeout
Soft key
Power off
Screen indication
Measure screen: ”Measure”
Measure screen:
Countdown counter
& “Delay to Start”
Measure screen: "HOLD"
Menu screen: Hold status
Measure screen:
!!
Measure screen:“Cleaning” &
“Cleaning phase & countdown
timer
”
–
Cal screen: cal.
related messages on
Man. Mode
screen: “Manual
Control”
Error screen: “Error
”
& “Error code”
Screen icons
Measure screen:
!
Measure screen:
Measure screen:
Measure screen:
!!
Measure screen:
Settings screen:
–
–
–
Main param.
reading
Blink
Last reading value except for
recovery phase where actual
reading value
–
–
–
Lot logging
Event
Event
Event
Event
Event
Event
Event
Event
Event logging
Ctrl. setpoint relay
Off
Off
Off
Off
Off
Off
Off
Off
HO
LD relay
(if
assign
ed)
Off
Off
On
Off
On
On
On
Off or On
On
RINSE relay
Off
Off
Off
Off
Operating
Off
Off
Off
Off
WASH relay
Off
Off
Off
Off
Operating
Off
Off
Off
–
Ctrl. set point
output
0 to 100%
0.0%
0.0%
0.0%
0.0%
0.0%
0.0%
0.0%
0.0%
Analog Out
assigned to Ctrl.
SetP
oint output
Scaled value of ctrl. output
Scaled value of ctrl.
output
Scaled value of ctrl. output
Scaled value of ctrl.output or
22mA
, if option enabled
Scaled value of last ctrl. output or a
fixed value of ctrl. output
Scaled value of
last ctrl. output
or fixed value of
ctrl. output
Scaled value of last
ctrl. output or fixed
value of ctrl. output
Any value in
the 0 to 22mA
range
Scaled value of ctrl
output
STATUS LED
HOLD L
ED