7. INSTALLATION
7.1. GENERAL GUIDELINES
•
HI510
Process Controller is suitable for outdoor use, but installation in direct sunlight or in areas of
extreme temperature is not recommended.
• Based on controller specifications, installation thermal conditions are in the -20 ºC to 50 ºC (-4 to
122 ºF) range.
• The controller should be installed in an area where vibrations and electromagnetic interference are
minimized.
• Unused cable conduit entries must be securely sealed with Type 4X or IP66 conduit plugs, to
maintain the ingress protection rating.
• Easy access to the controller should be available at all times.
• Safety precautions must be observed at all times! See SAFETY MEASURES section for details.
• The versatile
HI510
enclosure design supports surface or wall-mount, panel-mount and pipe-
mount installations.
7.2. WALL MOUNT (OR SURFACE MOUNT)
Wall-Mount Support Surface & Inside Depth Dimensions
• at least 208 mm (8.2 “)
wall support surface, if the mounting plate is mounted horizontally.
• at least 108 mm (4.3 “) wall support surface, if the mounting plate is mounted vertically.
170mm 6.7”
208mm 8.2”
34mm
1.3”
85mm
3.3”
160mm
6.3”
Figure 5:
Wall-Mount Panel, Slots Dimensions