Overtime (Setpoint must be enabled first)
Option:
Disabled, 10 to 120 minutes
The overtime (safety timer) parameter is provided to set the maximum continuous time a relay
running a pump or valve is energized. For a control that is running an On/Off algorithm and its output
is a relay, this time is the continuous time the relay is On before an alarm is issued. The timer will run
during the On relay period and is reset when the Set point is reached. If the timer period expires, the
relay will deactivate and an Alarm condition will occur.
With Overtime selected, press
Set
. Press the
keys to edit the present value, displayed blinking.
Control Output (Setpoint Must Be Enabled First)
Option:
Read only
Displays the current relay (e.g. Relay1) associated with selected Set point.
If
Multiple
is displayed, press
View
, to display assigned relays or outputs.
Minimum ON Time
Option:
1 to 10 seconds
Allows users to control the speed of the relay status change when previously set conditions are met.
This timer prevents the relay and connected device from “chattering” by forcing a minimum on and
off time.
The flashing of the selected value indicates that it can be modified by using the
keys. Press
Set,
to confirm value
Note:
The controller validates the configured Setup when attempting to exit menu and directs the
user to any invalid parameters. At prompt to save changes, press virtual key
YES
.