OPERATION
39
Wire gauge considerations
Background
Before connecting the output terminals to a
load, the wire gauge of the cables should be
considered.
It is essential that the current capacity of the
load cables is adequate. The rating of the cables
must equal or exceed the maximum current
rated output of the instrument.
Recommended
wire gauge
Wire Gauge Nominal Cross
Section
Maximum Current
20
0.5
9
18
0.75
11
18
1
13
16
1.5
18
14
2.5
24
12
4
34
10
6
45
8
10
64
6
16
88
4
25
120
2
32
145
1
50
190
00
70
240
000
95
290
0000
120
340
The maximum temperature rise can only be 60
degrees above the ambient temperature. The
ambient temperature must be less than 30
degrees.
To minimize noise pickup or radiation, the
load wires and remote sense wires should be
twisted-pairs of the shortest possible length.
Shielding of the sense leads may be necessary
in high noise environments. Where shielding is
Summary of Contents for APS-7000 Series
Page 1: ...Programmable AC Power Source APS 7000 Series USER MANUAL ISO 9001 CERTIFIED MANUFACTURER ...
Page 111: ...OPERATION 111 Simulate Example ...
Page 157: ...COMMUNICATION INTERFACE 157 Exit 6 Press Exit F4 to exit from the serial port settings ...
Page 187: ...APPENDIX 187 APS 7000 Dimensions APS 7050 402 545 5 430 110 4 87 9 Scale mm ...
Page 188: ...APS 7000 Series User Manual 188 APS 7100 561 6 705 5 430 110 4 87 9 Scale mm ...
Page 189: ...APPENDIX 189 APS 7200 402 5 310 5 429 8 682 4 649 2 Scale mm ...
Page 190: ...APS 7000 Series User Manual 190 APS 7300 491 5 399 5 429 8 682 4 649 2 Scale mm ...