GREE Photovoltaic Direct-driven Inverter Multi VRF Units
148
Fault code
Fault
Possible reasons
Solution
C2
Communication
failure between
main control board
and inverter
compressor drive
1. The communication cable is not
connected.
2. The communicator is
disconnected.
3. The communication cable is
poorly connected.
4. The communicator is faulty.
1) Check if the cable connecting the control board
and the compressor's drive board is loose. If yes,
reconnect it;
2) Check if the cable connecting the control board
and compressor's drive board is broken. If yes,
replace the cable;
3) Check the contact of the communication cable
connecting the control board and compressor's
drive board;
4) Replace the control board. If the fault is solved,
the control board is faulty. Replace the
compressor's drive board. If the fault is solved, the
compressor's drive board is faulty.
C3
Communication
failure between
main control board
and variable
frequency fan drive
1. The communication cable is not
connected.
2. The communicator is
disconnected.
3. The communication cable is
poorly connected.
4. The communicator is faulty.
1) Check if the cable connecting the fan's drive
board and the compressor's drive board is loose. If
yes, reconnect it;
2) Check if the cable connecting the fan's drive
board and compressor's drive board is broken. If
yes, replace the cable;
3) Check the contact of the communication cable
connecting the fan's drive board and compressor's
drive board;
4) Replace the control board. If the fault is solved,
the control board is faulty. Replace the fan's drive
board. If the fault is solved, the fan's drive board is
faulty.
C4
Malfunction of lack
of indoor unit
1. Some indoor units in the
system are not power-connected.
2. Communication wires of some
indoor units in the system are
disconnected or have loose
contact.
3. Controllers of some indoor
units in the system are abnormal.
1. Check the number of online indoor units through
outdoor unit and compare it with the number of
indoor units that are actually installed. Confirm the
number of missing indoor units.
2. Check whether all the indoor units are
power-connected. If some are not, connect them
to power. If power connection is fine, check further
whether there is any indoor unit that fails to display
on wired controller or receiver board. If such
indoor unit exists, it means its main board is
abnormal and needs to be replaced. If everything
said above is confirmed OK, continue to check
according to step 3.
3. The missing indoor units will display error “C0”
on wired controller or receiver board. Check the
communication wire of the missing indoor unit
whether it is disconnected or has loose contact. If
yes, connect the communication wire tightly. If
communication wire is OK, check whether it is
connected reversely. Power on the indoor unit
again and see if error “C0” occurs. If “C0” is
displayed, it means main board is abnormal and
needs to be replaced.
C5
Indoor unit project
number conflict
warning
1. Project numbers conflict with
each other.
1. Change conflicting project numbers and ensure
that no IDU's project number is repeated.
C6
Outdoor unit
number
inconsistency
warning
Communication cables between
ODUs are loose.
Communication cables between
ODUs are broken.
Communication cables between
ODUs are poorly connected.
4. The control board is faulty.
1. If the communication cable is loose, reconnect
it;
2. If the communication cable is broken, replace it;
3. Check contact of the communication cable;
4. Replace the control board.
Summary of Contents for GMV5 Series
Page 202: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 198 Troubleshooting ...
Page 253: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 249 Troubleshooting ...
Page 256: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 252 Troubleshooting ...
Page 262: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 258 Troubleshooting ...
Page 274: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 270 2 Check oil balancer ...
Page 287: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 283 ...
Page 321: ...JF00303868 ...