GREE Photovoltaic Direct-driven Inverter Multi VRF Units
128
Progress
Commissioning Code
Progress Code
Status Code
Meaning
LED1
LED2
LED3
Code Display Status Code Display Status Code Display Status
05_Internal
communication
detection
db
On
05
On
C2
On
The system detects
communication
failure between
master unit and
inverter compressor
driver.
db
On
05
On
C3
On
The system detects
communication
failure between
master unit and
inverter fan driver.
db
On
05
On
CH
On
The rated capacity
ratio is over-high
between indoor and
ODUs.
db
On
05
On
CL
On
The rated capacity
ratio is over-low
between indoor and
ODUs.
For details about the above troubleshooting method, refer to the "Troubleshooting Method" part.
Step 10: Unit commissioning step 06 is component detection for ODU.
If no exception is detected, the main board is displayed as follows and the unit automatically enters
the next commissioning step.
Progress
Commissioning Code
Progress Code
Status Code
Meaning
LED1
LED2
LED3
Code Display Status Code Display Status Code Display Status
06_Component
detection for ODU
db
On
06
On
OC
On
The system detects
that no ODU
component fails and
automatically enters
the next step.
If an exception is detected, the unit retains the current status and waits for manual troubleshooting.
Corresponding faults include:
Progress
Commissioning Code
Progress Code
Status Code
Meaning
LED1
LED2
LED3
Code Display Status Code Display Status
Code
Display Status
06_Component
detection for ODU
db
On
06
On
Corresponding
fault code
On
The system detects
component failure of
ODU.
For details about the above troubleshooting method, refer to the "Troubleshooting Method" part.
Step 11: Unit commissioning step 07 is component detection for IDU.
If no exception is detected, the main board is displayed as follows and the unit automatically enters
the next commissioning step.
Progress
Commissioning Code
Progress Code
Status Code
Meaning
LED1
LED2
LED3
Code Display Status Code Display Status Code Display Status
07_Component
detection for
IDU
db
On
07
On
OC
On
The system detects that no IDU
component fails and automatically
enters the next step.
If an exception is detected, the unit retains the current status and waits for manual troubleshooting.
Summary of Contents for GMV5 Series
Page 202: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 198 Troubleshooting ...
Page 253: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 249 Troubleshooting ...
Page 256: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 252 Troubleshooting ...
Page 262: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 258 Troubleshooting ...
Page 274: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 270 2 Check oil balancer ...
Page 287: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 283 ...
Page 321: ...JF00303868 ...