be reserved for maintenance.
(5) The riser should be installed in the air conditioning tube well, and the horizontal pipe should be
placed in the ceiling, if possible.
Always careful not to leak the refrigerant during welding.
The refrigerant generates poisonous gas harmful to human body if combusted.
Do not perform welding in a closed space.
Be sure to close the cap of the service port to prevent gas leakage after the work.
Please block the pipe knock outs of the front and side panels after installing the pipes (Animals or
foreign objects may be brought in to damage the cables.)
6.1.2 Processing to Refrigerant Pipes
6.1.2.1 Cut-off and Burring
Use a special-purpose pipe cutter to cut copper pipes instead of using a hacksaw.
Cut the pipes gently to ensure that the copper pipe does not deform.
After cutting the pipes, use a slicker to grater bur the pipes with the pipe opening inclining downward
so that the copper scales do not fall into the pipe.
Allowable deviation: Skewness of the cross section cannot exceed 1% of the copper pipe caliber.
If the copper pipe is not used immediately after cut-off, cover it with a sealing cap or adhesive tape.
6.1.2.2 Pipe Cleaning
Cleaning with a piece of silk cloth: Wrap a thin steel wire with a piece of clean silk cloth. Crumple the
cloth into a lump with diameter larger than the pipe calibre. Apply several drops of chlorylene to the cloth.
Push the cloth in from one end of the pipe and pull out from the other end. Every time the cloth is pulled
out, remove the dust and sundries with chlorylene. Wash repeatedly until the pipe is clean. This method
applies to straight pipes.
Cleaning with nitrogen: Blow off all dust and sundries in the pipe with nitrogen. This method applies
to coils.
After cleaning, cover the both ends of the pipe with a sealing cap or adhesive tape.
6.1.2.3 Pipe Bending
Processing methods:
Manual bending: applies
to thin copper pipes (Φ6.35 mm (1/4 in.) to Φ12.7 mm (1/2 in.))
Mechanical bending: applicable range (Φ6.35mm (1/4 in.) to Φ54.1mm (2
-1/4 in.))
Requirements:
The radius of the bending pipe must exceed 3.5D. The ratio of the short diameter after bending to
the original diameter must exceed 2/3.
Summary of Contents for GMV5 Series
Page 202: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 198 Troubleshooting ...
Page 253: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 249 Troubleshooting ...
Page 256: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 252 Troubleshooting ...
Page 262: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 258 Troubleshooting ...
Page 274: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 270 2 Check oil balancer ...
Page 287: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 283 ...
Page 321: ...JF00303868 ...