GREE Photovoltaic Direct-driven Inverter Multi VRF Units
111
The display is as follows:
LED1
LED2
LED3
Function Code Display Mode
Fault Sequence
Display Mode
Current Status
Display Mode
n6
On
01
On
Historical
fault/module
address
Displayed alternately
n6
On
02
On
Displayed alternately
n6
On
03
On
Displayed alternately
n6
On
04
On
Displayed alternately
n6
On
05
On
Displayed alternately
"01-05" indicates the fault sequence from the earliest to the latest.
If there are less than five historical faults, LED2 and LED3 display “00” indicating there are no more
historical faults after the last fault is displayed.
In fault query status, press and hold "SW7" for five seconds to clear all historical faults of the ODU.
Step 8: If the n7 parameter query is selected, the display is as follows. Enter the to-be-confirmed
status of parameter query.
LED1
LED2
LED3
Function Code
Display Mode
Current Progress/Mode
Display Mode
Current Status
Display Mode
n7
Blinking
00
Blinking
00
Blinking
On the master unit, press "SW7" to confirm parameter query and enter the module confirmation
status for parameter query. The display is as follows:
LED1
LED2
LED3
Function Code
Display Mode
Module Address
Display Mode
Current Status
Display Mode
n7
On
01
Blinking
00
Blinking
n7
On
02
Blinking
00
Blinking
n7
On
03
Blinking
00
Blinking
n7
On
04
Blinking
00
Blinking
Select a module for parameter query by pressing "SW1 (UP)" or "SW2 (DOWN)" and then press
"SW7". The display is as follows:
LED1
LED2
LED3
Function Code
Display Mode
Parameter Code
Display Mode
Current Status
Display Mode
n7
On
XX
On
Parameter value
Blinking
LED2 displays the parameter code of the module and LED3 displays the parameter value.
Parameters are displayed in the following sequence. By default, the outdoor environment temperature
value is displayed. Select a corresponding parameter value by pressing "SW1 (UP)" or "SW2 (DOWN)".
Parameter Code
Parameter Name
Unit
Remark
01
Outdoor environment temperature
°C
02
Operation frequency of compressor 1
Hz
03
Operation frequency of compressor 2
Hz
04
Operation frequency of outdoor fan
Hz
05
Module high-pressure
°C
06
Module low-pressure
°C
07
Discharge temperature of compressor 1
°C
08
Discharge temperature of compressor 2
°C
09
Discharge temperature of compressor 3
°C
This parameter is invalid for the
GMV5 series.
Summary of Contents for GMV5 Series
Page 202: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 198 Troubleshooting ...
Page 253: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 249 Troubleshooting ...
Page 256: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 252 Troubleshooting ...
Page 262: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 258 Troubleshooting ...
Page 274: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 270 2 Check oil balancer ...
Page 287: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 283 ...
Page 321: ...JF00303868 ...