GREE Photovoltaic Direct-driven Inverter Multi VRF Units
286
Removal procedure of compressor
Note: Before removing the compressor, make sure no refrigerant is inside the pipeline and power has
been disconnected.
Step
Diagram
Operation Procedure
9 . Check and
then install front
panels.
●Check various parts and
connection wires;
●If no problem is fo
und, hook the
front panels and tighten the
screws.
3.3.2 Disassembly and Assembly of 4
-way Valve
Removal procedure of 4
-way valve
Note: Before removing the 4-way valve, make sure no refrigerant is inside the pipeline and power has
been disconnected.
Step
Diagram
Operation Procedure
1
.
Loosen the
hooks at the
bottom of the
electric box and
the screws.
●Remove the upper and lower
front panels;
●Loosen the hooks at the bottom
of the electric box;
● Use a screwdriver to unscrew
the electric box.
2
、
Remove the
electric box.
●Disconnect internal and external
connection wires of the electric
box;
●Protect the internal parts during
the disassembly.
Summary of Contents for GMV5 Series
Page 202: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 198 Troubleshooting ...
Page 253: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 249 Troubleshooting ...
Page 256: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 252 Troubleshooting ...
Page 262: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 258 Troubleshooting ...
Page 274: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 270 2 Check oil balancer ...
Page 287: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 283 ...
Page 321: ...JF00303868 ...