Removal procedure of gas liquid separator
Note: Before removing the gas liquid separator, make sure no refrigerant is inside the pipeline and
power has been disconnected.
Step
Diagram
Operation Procedure
5. Install a new
gas liquid
separator.
●Put the gas liquid separator
based on the position of the
suction and discharge pipes and
weld the pipes with the gas liquid
separator;
●During welding, charge nitrogen
into the pipes. The pressure
should be controlled within
0.5±0.1kgf/cm
2
(relative
pressure). Note: Avoid nearby
parts from being burnt during
welding;
●Screw the gas liquid separator.
6. Fix and wire
the electric box.
●Put the electric box back to the
original position and screw it;
●Connect wires same as the
original.
7. Check and
install the front
panels.
●Check various par
ts and
connection wires;
●If no problem is found, hook the
front panels and tighten the
screws.
Summary of Contents for GMV5 Series
Page 202: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 198 Troubleshooting ...
Page 253: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 249 Troubleshooting ...
Page 256: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 252 Troubleshooting ...
Page 262: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 258 Troubleshooting ...
Page 274: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 270 2 Check oil balancer ...
Page 287: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 283 ...
Page 321: ...JF00303868 ...