GREE Photovoltaic Direct-driven Inverter Multi VRF Units
253
2.3.4.131 “U0” Insufficient compressor preheating time
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
If it is detected that the oil temperature preheating time of compressor before startup doesn’t reach 8
hours, it will report this error.
Possible reason
:
——
Troubleshooting:
The complete unit shall be preheated for more than 8 hours before startup.
2.3.4.132 “U2” ODU capacity DIP switch/jumper cap setting error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
ODU mainboard detects that the capacity code doesn’t comply with the actual unit capacity, or ODU
mainboard detects that the jumper cap value doesn’t comply with the actual unit
P
ossible reason
:
■Capacity DIP switch is wrong or jumper cap is wrong (for those models without jumper cap, it won’t
be detected)
■DIP switch or jumper cap is broken
■Detecting circuit is abnormal
Troubleshooting:
2.3.4.133 “U3” Power phase sequence protection
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
If phase loss or reverse of three-phase power is detected (e.g. incorrect connection of power supply
Summary of Contents for GMV5 Series
Page 202: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 198 Troubleshooting ...
Page 253: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 249 Troubleshooting ...
Page 256: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 252 Troubleshooting ...
Page 262: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 258 Troubleshooting ...
Page 274: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 270 2 Check oil balancer ...
Page 287: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 283 ...
Page 321: ...JF00303868 ...