GREE Photovoltaic Direct-driven Inverter Multi VRF Units
292
3.3.5 Disassembly and Assembly of Gas Liquid Separator
Removal procedure of gas liquid separator
Note: Before removing the gas liquid separator, make sure no refrigerant is inside the pipeline and
power has been disconnected.
Step
Diagram
Operation Procedure
1
.
Loosen the
hooks at the
bottom of the
electric box and
the screws.
●Remove the upper and lower
front panels;
●Loosen the hooks at the bottom
of the electric box;
● Use a screwdriver to unscrew
the electric box.
2. Remove the
electric box.
●
Disconnect internal and
external connection wires of the
electric box;
●Protect the internal parts during
the disassembly.
3. Disassemble
the gas liquid
separator.
●Heat the 2 connection pipes of
the gas liquid separator by
acetylene welding and then
remove the pipes. Note: Avoid
nearby parts from being burnt
during welding.
4. Remove the
gas liquid
separator.
●Unscrew and remove the gas
liquid separator.
Summary of Contents for GMV5 Series