GREE Photovoltaic Direct-driven Inverter Multi VRF Units
127
Progress
Commissioning Code
Progress Code
Status Code
LED1
LED2
LED3
Code
Display Status
Code
Display Status
Code
Display Status
03_Module quantity confirmation
db
On
03
On
OC
On
If the displayed quantity is inconsistent with the number of actually connected modules, check
whether communication cables are correctly connected between modules in power-off status. Then
perform commissioning again.
It is very important to correctly confirm the number of ODUs. If the confirmed quantity is
inconsistent with the actual quantity, the system may improperly run.
Step 8: When the unit runs to step 04, users need to manually confirm the number of indoor
modules. The main board of each module is displayed as follows:
Progress
Commissioning Code
Progress Code
Status Code
LED1
LED2
LED3
Code
Display Status
Code
Display Status
Code
Display Status
04_Indoor unit quantity
confirmation
db
On
04
On
Number of
connected IDUs
Blinking
If the displayed quantity is consistent with the number of actually connected modules, press "SW7"
on the master unit to confirm. The main board is displayed as follows and the unit automatically enters
the next commissioning step.
Progress
Commissioning Code
Progress Code
Status Code
LED1
LED2
LED3
Code Display Status Code Display Status
Code
Display Status
04_Indoor unit quantity confirmation
db
On
04
On
OC
On
It is very important to correctly confirm the number of IDUs. If the confirmed quantity is
inconsistent with the actual quantity, the system may improperly run.
Step 9: Unit commissioning step 05 is internal communication detection.
If no exception is detected, the main board is displayed as follows and the unit automatically enters
the next commissioning step.
Progress
Commissioning Code
Progress Code
Status Code
Meaning
LED1
LED2
LED3
Code Display Status Code Display Status Code
Display
Status
05_Internal
communication
detection
db
On
05
On
OC
On
The system completes
detection and automatically
enters the next step.
If an exception is detected, the unit retains the current status and waits for manual troubleshooting.
Corresponding faults include:
Summary of Contents for GMV5 Series
Page 202: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 198 Troubleshooting ...
Page 253: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 249 Troubleshooting ...
Page 256: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 252 Troubleshooting ...
Page 262: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 258 Troubleshooting ...
Page 274: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 270 2 Check oil balancer ...
Page 287: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 283 ...
Page 321: ...JF00303868 ...