GREE Photovoltaic Direct-driven Inverter Multi VRF Units
124
Progress Description for Commissioning Phases
——
Commissioning Code Progress Code
Status Code
Meaning
Progress
LED1
LED2
LED3
Code
Display
Status
Code Display
Status
Code
Display
Status
13_
—
—
—
—
—
—
No meaning.
14_
—
—
—
—
—
—
No meaning.
15_Cooling
operation by
manual perfusion
db
On
15
On
AC
On
The system is in cooling-mode
commissioning operation (the
system automatically selects the
commissioning operation mode
without needing manual settings).
db
On
15
On
Corresponding
fault code
On
A fault occurs on the cooling-mode
commissioning operation.
db
On
15
On
J0
On
A fault occurs on other modules
during the cooling-mode
commissioning operation.
db
On
15
On
U9
On
A fault occurs on ODU pipes or
valves.
db
On
15
On
XXXX/U8
On
The system detects pipe failure of
IDU. "XXXX" indicates the project
number of the faulty IDU. The fault
code "U8" is displayed after three
seconds. For example, if a U8 fault
occurs on IDU 100, LED3 will
circularly display "01", "00" (two
seconds later), and "U8" (two
seconds later).
16_Heating
operation by
manual perfusion
db
On
16
On
AH
On
The system is in heating-mode
commissioning operation (the
system automatically selects the
commissioning operation mode
without needing manual settings).
db
On
16
On
Corresponding
fault code
On
A fault occurs on the heating-mode
commissioning operation.
db
On
16
On
J0
On
A fault occurs on other modules
during the heating-mode
commissioning operation.
db
On
16
On
U9
On
A fault occurs on ODU pipes or
valves.
db
On
16
On
XXXX/U8
On
The system detects pipe failure of
IDU. "XXXX" indicates the project
number of the faulty IDU. The fault
code "U8" is displayed after three
seconds. For example, if a U8 fault
occurs on IDU 100, LED3 will
circularly display "01", "00" (two
seconds later), and "U8" (two
seconds later).
17_Commissioni
ng completion
status
01-04
On
OF
On
OF
On
The unit has completed
commissioning and in standby
status. LED1 displays the module
address; LED2 and LED3 display
"OF".
NOTE:
In commissioning status, press and hold "SW3" and "SW4" simultaneously for more than
five seconds to enter the no-wired-controller commissioning mode. In this mode, the system does not
detect the communication status between the wired controller and IDU.
2.3.3.2 Commissioning Operation Mode
The VRF provides three commissioning methods.
①
Commissioning through the main board of ODU
②
Commissioning on a PC through professional software. Parameters of the ODU and IDU can be
Summary of Contents for GMV5 Series
Page 202: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 198 Troubleshooting ...
Page 253: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 249 Troubleshooting ...
Page 256: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 252 Troubleshooting ...
Page 262: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 258 Troubleshooting ...
Page 274: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 270 2 Check oil balancer ...
Page 287: ...GREE Photovoltaic Direct driven Inverter Multi VRF Units 283 ...
Page 321: ...JF00303868 ...