GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
276
1.4.2.2 Hardware Installation
P
o
w
e
r i
n
p
u
t
Gateway
Running Alarm
Power
Address
Function
296mm
177mm
56mm
98.5mm
Length x Width x Height: 296 x 177 x 56 (mm)
The Modbus gateway should be located inside the electric cabinet, hung up with the front side facing
upwards and fixed with four bolts. See the following figure for the required clearance (only for reference).
Fixed with
four bolts
29
6m
m
177mm
Hung up with
the front side
facing upward
120mm
120mm
120mm
120mm
50
m
m
C
ab
le
tr
ou
gh
120mm
120mm
C
ab
le
tr
ou
gh
98.5mm
Electric cabinet
Gateway
Gateway
Gateway
Power input
The power input should be 100VAC-240VAC, 50/60Hz.
Do not touch the input port of the power supply when the gateway is energized.
Modbus gateway is recommended to install near air conditioning units so as to shorten their
communication distance. The maximum allowable communication distance of them is 500 m. For
the communication distance between Modbus gateway and Gree CAC Remote Monitoring
System/BMS system, we can use optoelectronic isolated repeaters for expansion.
The power lines and communication lines of Modbus gateways should be laid separately; otherwise,
Modbus gateways may become faulty. In the preceding figure, the thin dotted line indicates
communication lines and the thick dotted line indicates strong current lines; they are for reference
only.
Control cabinets should be designed to satisfy Modbus gateways both in number and layout as well
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...