GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
308
By default, ―A7‖ is displayed.
LED1
LED2
LED3
Function code Display mode Current progress Display mode Current state Display mode
A7
Flash
00
Flash
00
Flash
2. Press SW2 (▼) on the master
ODU to select the function code n5 (setting of IDU number
offset) and press SW7 to confirm. The following is displayed:
LED1
LED2
LED3
Function code Display mode Current progress Display mode Current state Display mode
n5
ON
00
Flash
00
Flash
3. While number offset waits for being confirmed, press SW7 to enter number offset state.
―Press SW7 to confirm" is displayed.
LED1
LED2
LED3
Function code Display mode Current progress Display mode Current state Display mode
n5
ON
00
ON
00
ON
In this case, all IDU numbers will be automatically offset. One minute later, conflict is
addressed and the system returns to normal. The offset can be set on only the master ODU
whose centralized control address is 0.
Note: If the quantity of conflict IDU numbers is not large, you are advised to manually set
them using Gree Debugger, control panel, or remote control. Manual setting is applicable to
intra-ODU conflicts only, not affecting numbers of other IDUs. If the quantity is large,
automatic offset is recommended, which is easy to realize. However, numbers of normal
ODUs may be altered. Automatic setting is applicable to initial installation and debug.
7.2 Communication Debug Between Modbus Gateways and Air Conditioning Units
Step 1: Set matched resistance of CAN2 bus.
ODU system 2
Master outdoor unit 1
ODU system 16
Master outdoor unit 1
ODU system 1
Master outdoor unit 1
……
With the matched
resistance
With the matched
resistance
Without the
matched resistance
Without the
matched resistance
CAN2 bus
Master ODU of Master ODU of Master ODU of
ODU system 1
ODU system 2 ODU system n
ODU system 2
Master outdoor unit 1
ODU system 16
Master outdoor unit 1
ODU system 1
Master outdoor unit 1
……
With the matched
resistance
With the matched
resistance
Without the
matched resistance
Without the
matched resistance
CAN2 bus
As shown in the preceding figure, the master ODU and the Modbus gateway at both ends of the CAN2
bus need to be configured with matched resistance.
The following figure shows how to set matched resistance on the Modbus gateway at the end of the
CAN2 bus:
8
With
matched
resistance
configured
Without
matched
resistance
configured
8
indicates the position
of toggle switch
Function
1
6
5
4
3
2
7
8
0
1
0
1
The following figure shows how to add matched resistance on the master ODU:
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...