GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
80
non-master unit is invalid, and it is unnecessary to change the settings.
3) The centralized control address DIP switch (SA2_Addr-CC) on the master unit of a refrigerating
system must be set to ―00000‖, and this system is the master sy
stem.
4) The centralized control address DIP switch (SA2_Addr-CC) on the master unit of other refrigerating
systems must be set as follows:
SA2
Address
No.
DIP1 DIP2 DIP3 DIP4 DIP5
1
0
0
0
0
2
0
1
0
0
0
3
0
0
1
0
0
4
0
0
0
1
0
5
0
0
0
0
1
6
1
0
0
0
1
7
0
1
0
0
1
8
0
0
1
0
1
9
0
0
0
1
1
10
1
0
0
1
1
11
0
1
0
1
1
12
0
0
1
1
1
13
1
0
1
1
1
14
0
1
1
1
1
15
1
1
1
1
1
16
5) The centralized control address DIP switch (SA2_Addr-CC) cannot be the same between different
refrigerating systems. Otherwise, address conflicts may occur and the unit cannot run properly.
3. Compressor Emergency Operation DIP Switch (SA3_COMP-E)
Corresponding to 2#-6# compressors, the compressor emergency operation DIP switch (SA3_COMP-E)
is used for aftersales emergency settings when an exception occurs on a compressor. It can shield the
operation of the abnormal compressor in a short time and guarantee the emergency operation of other
compressors.
When it is required to shield the operation of 2#-6# compressors upon failure, set the DIP switch
according to the following methods:
Compressor Emergency Operation
DIP Switch (SA3_COMP-E)
Remark
DIP1
DIP2 DIP3 DIP4 DIP5
0
0
0
0
0
Not shielding the operation of
2#-6# compressors
1
0
0
0
0
Shielding the operation of 2#
compressor
0
1
0
0
0
Shielding the operation of 3#
compressor
0
0
1
0
0
Shielding the operation of 4#
compressor
0
0
0
1
0
Shielding the operation of 5#
compressor
0
0
0
0
1
Shielding the operation of 6#
compressor
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...