GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
59
Equip a pressure regulator valve to the nitrogen cylinder.
The nitrogen flow is above 4-6 L/min (pressure of 0.02 to 0.05 MPa) and must be regulated based
on the pipe caliber.
3.6 Requirements on Manifold Installation
Manifolds are used to divert refrigerant. Requirements on manifold installation are as follows:
A. Ensure that the manifold is close to the IDU to reduce impact on refrigerant assignment by IDU
branches.
B. The manifold must be that specified by the manufacture and match with the devices.
C. Ensure that the manifold model is correct.
D. Manifolds can be laid in the following ways:
D1. Horizontal installation: The three ports must be on the same level. The shaping size and
assembly angle cannot be changed.
D2. Vertical installation: The direction can be upwards or downwards. Three ports must be on the
same elevation without inclination.
W
ith
in
±
1
5
°
W
ith
in
±
1
5
°
Diagram for direction A
Diagram for direction B
B
A
D3. The length of a straight pipe between two manifolds cannot be less than 500 mm.
D4. The length of a straight pipe before the main pipe port of the manifold cannot be less than 500
mm.
D5. The length of a straight pipe between the branch of the manifold and the IDU cannot be less
than 500 mm.
E. Fixing of manifolds.
There must be three fixing point for both horizontal and vertical installation of the Y-type manifold.
Fixing point 1: 100 mm on the main inlet manifold from the welding point
Fixing point 2: 200 mm on the main branched pipe from the welding point
Fixing point 3: 250 mm on the branched pipe from the welding point
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...