GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
91
Step 4: When the high-pressure value displayed on LED3 continually blinks (displayed as 0
C if the high
pressure is less than 0
C), quickly close the air-tube stop valve of the emergency module and then press
"SW7" on the master unit to confirm completing refrigerant recovery or power off the entire unit.
If no operations are performed after the high-pressure value displayed on LED3 continually blinks for
three minutes, the entire unit will be forcibly stopped.
On the master unit, press "SW6" to return to the upper level for restoring the standby status of the entire
unit (press "SW6" in setting status to return to the upper level; press "SW6" after settings are completed
to restore the normal operating status of the unit).
Note:
Before the basic module refrigerant recovery operation, users must close the liquid-tube stop
valve of the basic module requiring refrigerant recovery.
Another startup is not allowed within 10 minutes after refrigerant recovery.
A8 Aftersales vacuuming mode settings
Step 1: Confirm entering the A8 aftersales vacuuming mode settings. The master unit is displayed as
follows:
LED1
LED2
LED3
Function
Code
Display
Mode
Current
Progress
Display
Mode
Current
Status
Display
Mode
A8
On
00
Blinking
OC
Blinking
Enter the to-be-confirmed status of system vacuuming mode settings.
Step 2: Press "SW7" to confirm entering the to-be-confirmed status of system vacuuming mode settings.
All modules are displayed as follows:
LED1
LED2
LED3
Function
Code
Display
Mode
Current
Progress
Display
Mode
Current
Status
Display
Mode
A8
On
00
On
OC
On
Expansion valves and electromagnetic valves of all outdoor and IDUs are opened, and the entire unit
cannot be enabled.
Press "SW6" on the master unit to quit the vacuuming status. Alternatively, the entire unit quits the
vacuuming status after 24 hours.
n0 System conservation operation settings
Step 1: Confirm entering the n0 system conservation operation settings. The master unit is displayed as
follows:
LED1
LED2
LED3
Function Code Display Mode Code Display Mode Current Status Display Mode
n0
On
01
Blinking
OC
Blinking
Step 2: Select a corresponding mode by pressing "SW1 (UP)" or "SW2 (DOWN)".
LED1
LED2
LED3
Function Code Display Mode Code Display Mode Current Status Display Mode
n0
On
01
Blinking
OC
Blinking
n0
On
02
Blinking
OC
Blinking
Step 3: Press "SW7" to confirm selecting the mode. The master unit is displayed as follows:
LED1
LED2
LED3
Function Code Display Mode Code Display Mode Current Status Display Mode
n0
On
01
On
OC
On
n0
On
02
On
OC
On
If no button operations are performed for five minutes, the function setting automatically quits and the
unit restores the current status. (Press "SW6" in setting status to return to the upper level; press "SW6"
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...