GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
236
12
1159
1.15
68
4548
4.763
13
1193
1.186
69
4639
4.86
14
1228
1.224
70
4731
4.958
15
1263
1.261
71
4893
5.13
3.2 Low-pressure sensor (R410a)
Temperature
(°C)
Absolute pressure
(kPa)
Voltage
(V)
Temperature
(°C)
Absolute pressure
(kPa)
Voltage
(V)
-70
36
0.369
-14
502
1.301
-69
38
0.373
-13
520
1.337
-68
40
0.377
-12
538
1.373
-67
43
0.383
-11
558
1.413
-66
46
0.389
-10
577
1.451
-65
48
0.393
-9
597
1.491
-64
51
0.399
-8
618
1.533
-63
54
0.405
-7
639
1.575
-62
57
0.411
-6
661
1.619
-61
61
0.419
-5
684
1.665
-60
64
0.425
-4
707
1.711
-59
68
0.433
-3
730
1.757
-58
72
0.441
-2
754
1.805
-57
76
0.449
-1
799
1.895
-56
80
0.457
0
804
1.905
-55
84
0.465
1
830
1.957
-54
89
0.475
2
857
2.011
-53
94
0.485
3
884
2.065
-52
99
0.495
4
912
2.121
-51
104
0.505
5
940
2.177
-50
109
0.515
6
969
2.235
-49
115
0.527
7
999
2.295
-48
121
0.539
8
1030
2.357
-47
127
0.551
9
1061
2.419
-46
133
0.563
10
1096
2.489
-45
140
0.577
11
1125
2.547
-44
146
0.589
12
1159
2.615
-43
154
0.605
13
1193
2.683
-42
161
0.619
14
1228
2.753
-41
168
0.633
15
1263
2.823
-40
176
0.649
16
1300
2.897
-39
184
0.665
17
1337
2.971
-38
193
0.683
18
1375
3.047
-37
202
0.701
19
1413
3.123
-36
211
0.719
20
1453
3.203
-35
220
0.737
21
1493
3.283
-34
230
0.757
22
1535
3.367
-33
240
0.777
23
1577
3.451
-32
250
0.797
24
1620
3.537
-31
261
0.819
25
1664
3.625
-30
272
0.841
26
1708
3.713
-29
283
0.863
27
1754
3.805
-28
295
0.887
28
1801
3.899
-27
307
0.911
29
1848
3.993
-26
319
0.935
30
1897
4.091
-25
332
0.961
31
1946
4.189
-24
345
0.987
32
1996
4.289
-23
359
1.015
33
2048
4.393
-22
373
1.043
34
2100
4.497
-21
388
1.073
35
2153
4.603
-20
403
1.103
36
2208
4.713
-19
418
1.133
37
2263
4.823
-18
434
1.165
38
2320
4.937
-17
450
1.197
39
2377
5.051
-16
467
1.231
40
2439
5.175
-15
484
1.265
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...