GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
93
follows:
LED1
LED2
LED3
Function Code
Display Mode
Current Progress/Mode
Display Mode
Current Status
Display Mode
n5
On
00
Blinking
00
Blinking
Step 2: Press "SW7" to send the project number offset command. The master module is displayed as
follows:
LED1
LED2
LED3
Function Code
Display Mode
Current Progress/Mode
Display Mode
Current Status
Display Mode
n5
On
00
On
OC
On
After 10 seconds, the system quits this mode and restores the normal operation mode.
Note: This function only needs to be set on the master system, which is the system with the centralized
control address SA2 DIP switch being "00000". For details, see the "Centralized Control Address DIP
Switch (SA2_Addr-CC)" section.
2. Function Query Operations
Step 1: Open the commissioning window of the master unit panel.
Step 2: Power on the entire unit.
Step 3: Press "SW4" on the master unit to enter the query status.
Step 4: Select a function to be queried by pressing "SW1 (UP)" or "SW2 (DOWN)" on the master unit. By
default, the A7 outdoor silent mode is displayed for query.
For example, select the A6 unit cooling/heating function. The display is as follows:
LED1
LED2
LED3
Function
Code
Display
Mode
ODU Function Mode
Code
Display
Mode
ODU Function Mode
Code
Display
Mode
A6
On
nA
On
nA
On
Step 5: If the n8 IDU address query is selected, the display is as follows. Enter the to-be-confirmed
status of IDU project number query.
LED1
LED2
LED3
Function
Code
Display
Mode
Current
Progress/Mode
Display
Mode
Current
Status
Display
Mode
n8
Blinking
00
Blinking
00
Blinking
Press "SW7" and select the IDU project number query on the master unit. The master unit is displayed
as follows. Other modules are displayed in normal status.
LED1
LED2
LED3
Function
Code
Display
Mode
Current
Progress/Mode
Display
Mode
Current
Status
Display
Mode
n8
On
00
On
00
On
Regardless of the current display status of wired controllers or display panels of all IDUs, the current
display status is all switched to the IDU project number. However, it does not influence the settings and
operation status of outdoor and IDUs.
On the master unit, press "SW6" to return to the upper level. The IDU retains the project number display
status.
On the master unit, press and hold "SW6" to quit the address display status for all IDUs and return to the
upper level.
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...