GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
235
54
15.173
1.311
145
1.0429
2.988
55
14.618
1.34
146
1.0197
2.995
56
14.085
1.37
147
0.9971
3.001
57
13.575
1.4
148
0.9752
3.007
58
13.086
1.429
149
0.9538
3.013
59
12.617
1.459
150
0.9331
3.018
60
12.368
1.475
3. Voltage / pressure lists of pressure sensors
3.1 High-pressure sensor (R410a)
Temperature (°C)
Absolute pressure (kPa) Voltage (V) Temperature (°C)
Absolute pressure (kPa) Voltage (V)
-40
176
0.102
16
1300
1.3
-39
184
0.111
17
1337
1.34
-38
193
0.12
18
1375
1.38
-37
202
0.13
19
1413
1.421
-36
211
0.139
20
1453
1.463
-35
220
0.149
21
1493
1.506
-34
230
0.16
22
1535
1.551
-33
240
0.17
23
1577
1.596
-32
250
0.181
24
1620
1.641
-31
261
0.193
25
1664
1.688
-30
273
0.206
26
1708
1.735
-29
283
0.216
27
1754
1.784
-28
295
0.229
28
1801
1.834
-27
307
0.242
29
1848
1.884
-26
319
0.255
30
1897
1.937
-25
332
0.268
31
1946
1.989
-24
345
0.282
32
1996
2.042
-23
359
0.297
33
2048
2.098
-22
373
0.312
34
2100
2.153
-21
388
0.328
35
2153
2.21
-20
403
0.344
36
2208
2.268
-19
418
0.36
37
2263
2.327
-18
434
0.377
38
2320
2.388
-17
450
0.394
39
2377
2.448
-16
467
0.412
40
2436
2.511
-15
484
0.43
41
2495
2.574
-14
502
0.45
42
2556
2.639
-13
520
0.469
43
2618
2.705
-12
538
0.488
44
2681
2.772
-11
558
0.509
45
2745
2.841
-10
577
0.53
46
2810
2.91
-9
597
0.551
47
2876
2.98
-8
618
0.573
48
2944
3.053
-7
639
0.596
49
3013
3.126
-6
661
0.619
50
3083
3.201
-5
684
0.644
51
3154
3.277
-4
707
0.668
52
3226
3.353
-3
730
0.693
53
3300
3.432
-2
754
0.718
54
3374
3.511
-1
779
0.745
55
3450
3.592
0
804
0.772
56
3528
3.675
1
830
0.799
57
3606
3.759
2
857
0.828
58
3686
3.844
3
884
0.857
59
3767
3.93
4
912
0.887
60
3849
4.018
5
940
0.917
61
3932
4.106
6
969
0.947
62
4017
4.197
7
999
0.979
63
4103
4.288
8
1030
1.012
64
4190
4.381
9
1061
1.046
65
4278
4.475
10
1093
1.08
66
4367
4.57
11
1125
1.114
67
4457
4.666
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...