GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
362
connect the communication
interfaces.
Though lines are
normal, a software
communication fault
occurs and some or
all units' information
is not displayed.
ODUs, after being replaced with
chips or reset with DIP, are not
re-powered on.
Re-power on the ODUs.
Matched resistance is not
configured.
Refer to the network
topology in the BACnet
Technical Manual to
configure matched
resistances.
After gateway IP addresses are
modified, the gateways are not
re-powered on.
Re-power on the gateways.
The unit address configured by
the software is inconsistent with
the actual address of units.
Modify unit address
settings.
Units are not powered on.
Power on the units.
ODUs or IDUs are not equipped
with chips, or chips are inversely
installed.
Install the chips in a correct
direction and power on the
units.
Unit address is incorrect or
replicate.
Correct the incorrect
address settings.
Though lines and
devices are normal,
information of
devices of a floor is
not displayed.
The maximum distance between
a gateway and its directly
connected ODUs exceeds 500 m.
Control the distance within
500m.
The number of the first unit is
incorrect.
Refer to the BACnet
Technical Manual to reset
the number.
Lines, devices, and
setups are all normal.
However, a software
communication fault
alarm is reported.
The display or controller does not
match units.
Check the models of the
controller and operation
panel. If they do not match
unit specification, replace
them.
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...