GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
58
The minimum distance between supports, hangers, and brackets is listed in the table below:
External Diameter of the
Pipe (mm)
ф≤16
40>ф≥19.05
ф≥40
Distance between
Horizontal Pipes (mm)
1000
1500
2000
Distance between Vertical
Pipes (mm)
1500
2000
2500
The pipe led through a wall or beam must be fixed by a support, hanger, or bracket on both ends at
the position 300 mm away from the hole.
3.4 Pipe Connection
3.4.1 Flaring Connection
The refrigerant pipes and IDUs are connected by using the flare opening. Therefore, the quality of
flaring connection must be ensured. The flaring depth of the bell mouth cannot be smaller than the
caliber. The flaring direction must face towards the direction of medium flow. Use two torque wrenches to
fasten the connection.
3.4.2 Socket Welding
The gap between socket components should be proper to ensure that the connection will not loose
from the friction surface. The flaring direction of the socket component must face towards the direction of
medium flow .During pipe connect, protect the braze welding part according the length specified below:
A: External Diameter of
the Pipe (mm)
B: Minimum Insertion
Depth (mm)
D-A: Gap between Pipes
(mm)
ф6.35
6
0.05-0.21
ф9.52
ф12.7
7
ф15.8
8
0.05-0.27
ф19.05
ф22.2
ф25.4
10
ф28.6,
ф31.8
12
0.05-0.30
ф38.1
ф44.5
19
0.15-0.35
ф54.1
24
0.15-0.35
3.4.2 Bell Socket Welding
The bell socket welding is another form of socket welding. It uses the sleeve or pipe in a larger size
for welding. The insertion depth cannot be smaller than that required by socket welding.
3.4.5 Flange Connection
The pipes with large caliber and the devices are always connected by using a flange, which must be
clean and intact. Before installation, apply lubricant on the surface of the flange. Two flanges must be
symmetrical. Fasten with screws at the diagonal direction to avoid inclination.
3.5 Welding Protection
Aerate with nitrogen before and during welding and keep aerating for 30 s after the welding is
finished.
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...