GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
81
Precautions:
A. When the DIP switch setting is not covered in the above scope, a DIP switch setting exception fault
may occur.
B. Only one compressor can be set to emergency mode on a module.
C. The compressor emergency operation mode is valid only in a single-module multi-compressor
system.
D.
The default factory setting is ―00000‖.
E. The system cannot continually run for more than 24 hours in compressor emergency operation status.
Once 24 hours are exceeded, the entire unit will be forcibly stopped and the limited operation code ―Ad‖
is displayed on the IDU.
F. 1#-6# compressors are defined from right to left facing the front of the unit.
4. 1# Compressor/Module Emergency Operation DIP Switch (SA4_I/M-E)
The 1# compressor/module emergency operation DIP switch (SA4_I/M-E) is used for aftersales
emergency settings when an exception occurs on the 1# compressor/module. It can shield the operation
of the abnormal compressor/module in a short time and guarantee the emergency operation of other
compressors.
When it is required to set the 1# compressor/module to emergency mode, set the DIP switch as follows:
1# Compressor/Module Emergency Operation
DIP Switch (SA4_I/M-E)
DIP1 DIP2
Remark
0
0
Not shielding the operation of 1#
compressor/module
1
0
Shielding the operation of 1#
compressor
0
1
Shielding the operation of the
module
Precautions:
A. When the DIP switch setting is not covered in the above scope, a DIP switch setting exception fault
may occur.
B. Only one compressor can be set to emergency mode on a module.
Subsequent to emergency
operation, valves of shielded outdoor unit, including the gas pipe, liquid pipe and oil balance pipe, need
to be closed tight by hand.
C. The compressor emergency operation mode is valid only in a single-module multi-compressor
system.
D. The module emergency operation mode is valid only in a system with more than two modules
connected in parallel.
E. Only one module can be set to emergency operation mode in each system.
F. The default factory setting is ―00‖.
G. The system cannot continually run for more than 24 hours in compressor emergency operation status.
Once 24 hours are exceeded, the entire unit will be forcibly stopped and the limited operation code ―Ad‖
is displayed on the IDU.
H. The system cannot continually run for more than 48 hours in module emergency operation status.
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...