GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
11
Electrical Parameters of High-static-pressure Air-duct-type Air Conditioner
Model
Power Supply
Circuit Breaker Capacity
(A)
Minimum Sectional Area
(mm²) of Grounding Wire
GMV-ND56PHS/A-T
220-240V~50Hz/208-230V~60Hz
6
1.0
GMV-ND63PHS/A-T
220-240V~50Hz/208-230V~60Hz
6
1.0
GMV-ND71PHS/A-T
220-240V~50Hz/208-230V~60Hz
6
1.0
GMV-ND80PHS/A-T
220-240V~50Hz/208-230V~60Hz
6
1.0
GMV-ND90PHS/A-T
220-240V~50Hz/208-230V~60Hz
6
1.0
GMV-ND100PHS/A-T
220-240V~50Hz/208-230V~60Hz
6
1.0
GMV-ND112PHS/A-T
220-240V~50Hz/208-230V~60Hz
6
1.0
GMV-ND125PHS/A-T
220-240V~50Hz/208-230V~60Hz
6
1.0
GMV-ND140PHS/A-T
220-240V~50Hz/208-230V~60Hz
6
1.0
GMV-ND160PHS/A-T
220-240V~50Hz/208-230V~60Hz
6
1.0
GMV-ND224PH/A-T
220-240V~50Hz/208-230V~60Hz
10
1.0
GMV-ND280PH/A-T
220-240V~50Hz/208-230V~60Hz
10
1.0
Note:
(1) The circuit breaker and power cable specifications are selected based on the maximum power
(maximum current) of the units.
(2) The power cable specifications are obtained under the conditions that the ambient temperature is
40
℃
, the working temperature of multi-core copper cable (for example, YJV cable) is 90
℃
, and the
cable is exposed in cable troughs. In different applications, adjust the specifications based on national
standards.
(3) Only copper conductor cable can be used.
(4) The sectional area of a wire is applicable for a distance range of up to 15 m. If the distance is greater
than 15 m, increase the sectional area of the wire correspondingly to prevent the wire from being burned
due to overload current and to avoid fire.
(5) The circuit breaker specifications are obtained under the conditions that the ambient temperature is
40
℃
when the circuit breaker is working. In different applications, adjust the specifications based on the
circuit breaker manual.
(6) The circuit breaker must support magnetic release and thermal release at the same time to protect
the system from short circuit and overload.
Electrical Parameters of Fresh Air Conditioning IDU
Mode
Power Supply
Specification
Circuit Breaker
Capacity/A
Minimum Sectional
Area of Grounding
Wire/mm
2
Minimum Sectional
Area of Power
Cable/mm
2
GMV-NX140P/A(X1.2)-K
220-240V
~
50Hz
6
1.0
1.0
GMV-NX224P/A(X2.0)-M
380-415V
~
50Hz
6
1.0
1.0
GMV-NX280P/A(X2.5)-M
380-415V
~
50Hz
6
1.0
1.0
GMV-NX280P/A(X3.0)-M
380-415V
~
50Hz
6
1.0
1.0
GMV-NX450P/A(X4.0)-M
380-415V
~
50Hz
10
1.0
1.0
Notes:
(
1
)
. The circuit breaker and power cable specifications in the above table are selected according to the
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...