GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
122
IV. References for Proper Unit Operation
Parameters
SN
Commissioning Item
Parameter
Name
Unit
Reference Value
1
System
parameter
Outdoor
unit
parameter
Outdoor
environment
temperature
°C
——
2
Discharge pipe
temperature of
compressor
°C
●When the system compressor is
running, the normal discharge
pipe or top temperature for
cooling is 70-95°C, which is more
than 10°C higher than the
saturation temperature
corresponding to the system
high-pressure. The normal
temperature for heating is
65-80°C, which is more than
10°C higher than the saturation
temperature corresponding to the
system high-pressure.
3
Defrosting
temperature
°C
●When the system runs for
cooling, the defrosting
temperature is 5-11°C lower than
the system high-pressure value.
●When the system runs for
heating, the defrosting
temperature is 2°C higher or
lower than the system
low-pressure value.
4
System
high-pressure
°C
●The normal system
high-pressure value is 20-55°C.
With the change of environment
temperature and system
operation capacity, the system
high-pressure value is 10-40°C
higher than the environment
temperature. The higher the
environment temperature, the
less the temperature difference.
●When the system runs for
cooling with the environment
temperature being 25-35°C, the
system high-pressure value is
44-53°C.
●When the system runs for
cooling with the environment
temperature being -5 to 10°C, the
system high-pressure value is
40-52°C.
5
System
low-pressure
°C
●When the system runs for
cooling with the environment
temperature being 25-35°C, the
system low-pressure value is
0-8°C.
●When the system runs for
cooling with the environment
temperature being -5 to 10°C, the
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...