GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
172
Part 3 Key Parts Maintenance
I. Cautions on Controller AP1 Replacement
1. Cautions on ODU AP1 Replacement
1.1 Distinguishing Master Module from Slave Module
Before replacing ODU AP1, determine the module is a master ODU or a slave ODU. They can be
distinguished based on:
①
―Master module DIP state (
SA8_MASTER-S
)‖
Every cooling system has only one master module (set in power-
off state). When a DIP is ―ON‖, the
corresponding position is ―0‖; when the DIP is ―OFF‖, the corresponding position is ―1‖. If
SA8_MASTER-
S is set to ―00‖, it indicates a master module; if it is set to ―10‖, it indicates a
slave module
(as shown in the figure below).
DIP setting
position
DIP setting
position
DIP setting
position
DIP setting
position
Master module state
Slave module state
②
AP1 LED
When a master module is powered on, LED1 is displayed as ―01‖. For a slave module, LED1 is
displayed as ―02‖, ―03‖ or ―04‖ (as shown in the figure below).
LED1 display state
Master module state
LED1 display state
Slave module state
LED1 display state
Slave module state
LED1 display state
Slave module state
Or
Or
1.2 Cautions on Replacement of Master ODU AP1
Before replacing master module AP1, make the following preparations:
①
Master module DIP setting
Set the new AP1 identical to the faulty AP1. Note that settings must be performed when the master ODU
is powered off and they will take effect after the ODU is powered on. Settings that are performed in
power-on state are invalid.
②
Communication state check
After AP1 DIP setting and all wiring, power on the master ODU AP1 and check whether D3 and D4 LEDs
are flashing. See the figure below:
Power
Run
D1
D2
D3
D4
D5
D6
D7
D8
Power
Running
IDU and ODU
communication
Main
system
M a i n -
system
Reserved
ODU
→
IDU
ODU
→
IDU
Inter-system
communication
System1
→
System2
System1
→
System2
If the LEDs flash, the ODU and IDUs normally communicate; if the LEDs are steadily on, communication
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...