8. Master Unit Setting DIP Switch (SA8_MASTER-S)
The master unit setting DIP switch (SA8_MASTER-S) defines module management of a system. A
master unit must be set, and only one master unit can be set in each refrigerat ing system (in
power-off status). The setting methods are as follows:
Master Unit Setting DIP Switch
(SA8_MASTER-S)
DIP1 DIP2
Remark
0
0
Master unit
1
0
Sub-module
Upon factory departure, all modules are in ―00‖ master unit status by default. When mult
iple modules are
connected in parallel, only one module retains the master unit status and other modules are set to
sub-module status. When a module is independently used, it uses the factory settings.
For the basic module set to master unit, the module ad
dress is displayed as ―01‖ on the main board.
Precautions:
A. When the DIP switch setting is not covered in the above scope, a DIP switch setting exception fault
may occur.
B. A module must be set to master unit status, and only one module can be set to master unit status in
each refrigerating system. Other modules are set to sub-module status.
C. Settings must be performed in power-off status.
D. The default factory setting is "00" master unit status.
9. DIP Switch Example
A. Explanation of DIP switch positions
On the DIP switch, ―ON‖ indicates ―0‖ status and the opposite direction indicates "1‖ status.
The position of white lever indicates the position to be set to.
B. Example
The following takes master unit settings as an example. Assume that a system consists of three modules:
module a, module b, and module c. Set module c to master unit and the other two modules to
sub-modules. The settings are as follows:
(II) System Function Button Operations
Module c (Master Module)
Module a/Module b (Sub-module)
Note:
System function settings and query must be performed after commissioning of the entire unit.
System function settings and query can be used no matter whether the entire unit runs.
1. Introduction to Function Buttons
The main board AP1 of the ODU consists of eight function buttons:
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...