GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
279
3. Connection Steps
(1) Connection between the Modbus gateway and the Gree web-based remote monitoring and control
system
Step 1: confirm the first Modbus gateway (Modbus gateway 1) to be connected to the Gree web-based
remote monitoring and control system, and then connect RS485-1 interface R+ and R- of this Modbus
gateway to the optoelectric converter interface R+ and R- or BMS through communication lines. (see
①
)
Step 2: connect RS485-1 interface R+ and R- of Modbus gateway 1 to the second Modbus gateway
(Modbus gateway 2) RS485-1 interface R+ and R- through communication lines. (see
②
)
Step 3: follow the same way as in Step 2 to connect other Modbus gateways in series. (see
③
)
(2) Connection between the Modbus gateway and the air conditioning system
Step1: confirm the master units to be connected to each Modbus gateway. Serial connection should be
applied as described in Section 5.2.2.(2) Communication lines between the Modbus gateway and the air
conditioning system. (see
④
)
Step 2: connect the Modbus gateway‗s CAN interface G1 and G2 to the interface G1 and G2 at the
terminal board of the corresponding master unit. (see
⑤
)
Step 3: when two Modbus gateways (gateway 2 and gateway 3) are required for one CAN2 network,
connect one gateway's (gateway 2) CAN interface G1 and G2 to the interface G1 and G2 at the terminal
board of the master unit, and then connect the other gateway's (gateway 3) interface G1 and G2 to the
interface G1 and G2 of the former gateway (gateway 2). (see
⑥
and
⑦
)
※
CAN2 network: Please refer to the system network diagram.
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...