GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
46
Equivalent length from the first branch to the furthest piping (1)
≤40
L6+L7+L8+L9+j
Height difference
between outdoor
unit and indoor unit
Outdoor unit at upper(4)
≤90
——
Outdoor unit at lower(4)
≤90
——
Height difference between indoor units (m)
≤30
——
Maximum length of Main pipe(2)
≤90
L1
From IDU to its nearest branch (3)
≤10
a,b,c,d,e,f,g,h,i,j
Notices:
(
1
)
. Normally, the pipe length from the first branch of IDU to the farthest IDU is 40m. When those
three conditions as below are satisfied, the length can reached 90m.
①
Actual length of pipe in total: L1+L2x2+L3x2+L4x2+…+L9x2+a+b+…+i+j≤1000m;
②
Length between each IDU and its nearest branch a, b, c, d, e, f, g, h, i, j≤40m;
③
Difference between the pipe length from the first branch of IDU to the farthest IDU and the
pipe length from the first branch of IDU to the nearest IDU: L10-
L11≤40m.
(
2
)
.
When the maximum length of the main pipe from ODU to the first branch of IDU is≥90m, then
adjust the pipe size of the gas pipe and liquid pipe of main pipe according to the following table.
Outdoor Model
Gas pipe size(mm)
Liquid pipe size(mm)
GMV-224WM/B-X
No need to enlarge pipe size
No need to enlarge pipe size
GMV-280WM/B-X
No need to enlarge pipe size
Φ12.7
GMV-335WM/B-X
Φ28.6
Φ15.9
GMV-400WM/B-X
Φ31.8
Φ15.9
GMV-450WM/B-X
Φ31.8
Φ15.9
GMV-504WM/B-X
Φ34.9
Φ19.05
GMV-560WM/B-X
Φ34.9
Φ19.05
GMV-615WM/B-X
Φ34.9
Φ19.05
GMV-680WM/B-X
No need to enlarge pipe size
Φ19.05
GMV-730WM/B-X
Φ38.1
Φ22.2
GMV-785WM/B-X
Φ38.
1
Φ22.2
GMV-850WM/B-X
Φ38.1
Φ22.2
GMV-900WM/B-X
Φ38.1
Φ22.2
GMV-960WM/B-X
Φ41.3
Φ22.2
GMV-1010WM/B-X
Φ44.5
Φ22.2
GMV-1065WM/B-X
Φ44.5
Φ22.2
GMV-1130WM/B-X
Φ44.5
Φ22.2
GMV-1180WM/B-X
Φ44.5
Φ22.2
GMV-1235WM/B-X
Φ44.5
Φ22.2
GMV-1300WM/B-X
Φ44.5
Φ22.2
GMV-1350WM/B-X
Φ44.5
Φ22.2
GMV-1410WM/B-X
Φ44.5
Φ25.4
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...