GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
150
Feedback
from user
Exception
Possible reasons
Solution
Primary reason
Secondary reason
Tertiary reason
Descript
ion
Confirm
ation
method
Descripti
on
Confirm
ation
method
Descrip
tion
Confirm
ation
method
Poor
heating/co
oling
performan
ce
A. When
the IDU is
working in
the
cooling
mode and
the
electronic
expansio
n valve is
opened to
2000PLS,
the
exhaust
temperatu
re of the
IDU's coil
is more
than 5
°C
higher
than the
intake
temperatu
re; B.
when the
IDU is
working in
the
heating
mode and
the
electronic
expansio
n valve is
opened to
2PLS, the
intake
temperatu
re of the
IDU's coil
is more
than 12
°C
lower
than the
saturation
temperatu
re
correspon
ding to
the high
pressure;
1. The
stop
valve of
the
ODU is
not fully
opened
as
required
.
——
——
——
——
Manual
check
Fully
open the
stop
valve.
2. The
system
pipeline
is
blocked.
——
2.1. The
system
air
pipeline
is
blocked.
Touch
the pipe
along
the
flowing
direction
of
refrigera
nt to feel
the
temperat
ure
differenc
e. The
differenc
e is
large.
2.1.1
The
block is
caused
by
solder.
Cut off
the pipe
and
check it.
Replace
and
solder
the pipe.
2.1.2
The
pipeline
is
blocked
by
impuriti
es.
Replace
and
solder
the pipe.
2.2 The
fluid pipe
is
blocked.
Touch
the pipe
along
the
flowing
direction
of
refrigera
nt to feel
the
temperat
ure
differenc
e. The
differenc
e is large
or part of
the pipe
is
frosting.
——
——
Replace
and
solder
the pipe.
2.4 The
pipe that
connects
the IDU
is
blocked.
Touch
the pipe
along
the
flowing
direction
2.4.1
The
block is
caused
by
solder.
Cut off
the pipe
and
check it.
Replace
and
solder
the pipe.
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...