GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
37
5. During the installation of the ODU, induced and exhaust pipes must be connected. In addition, the
aperture opening rate of shutters must be at least 80%, and the angle between the shutters and the
horizontal plane should be less than 20°. Requirements for installing exhaust air duct are as follows:
i.
Basic requirement for connecting an ODU to static pressure ventilating duct
When an ODU needs to be connected to the static pressure ventilating duct, the ventilating duct must be
reasonably designed. The pressure loss caused by the ventilating duct must be calculated. In addition, a
proper type of ventilating duct is necessary. To connect he static pressure ventilating duct to the ODU,
three basic parts are required: (1) ODU; (2) canvas; and (3) steel-plate ventilating duct. The ODU must
be interconnected with the ventilating duct through canvas to prevent abnormal vibration and noise
generated by the steel-plate ventilating duct. The joint part must be tightly sealed with tin foil to avoid air
leakage.
ii.
Preparations for connecting an ODU to static pressure ventilating duct
(1) The ODU is installed properly based on the unit installation requirement.
(2) The steel-plate ventilating duct is designed based on the unit and engineering requirement, and is
installed properly according to the engineering standards.
(3) Based on the unit dimensions and the size of steel-plate ventilating duct, prepare materials such as
canvas casing, tin foil, steel bar and tapping screw, as well as tools such as hand-operated electric drill,
air screw driver and screwdriver.
iii.
Basic operation of connecting an ODU to static pressure ventilating duct
Two methods are available to connect an ODU to static pressure ventilating duct.
Method 1: Reserve the unit top case. Detailed operations are as follows:
a)
Install the ODU (2) and steel-plate ventilating duct (1). Use an air screw driver or screwdriver to
unfasten the tapping screws that fixing the top case component (3), and then remove the top case
component. Take out the grille from the top of the top case component and leave the top case.
b)
Put the canvas casing inside out (4). Cover one end of the canvas casing over the unit
downward until the canvas end face is aligned with the unit or a bit higher than the top of the unit. Then,
put the top case back (3) and tightly press the canvas casing (4). Use tapping screws to fix the top case
onto the unit (3).
c)
Pull up the canvas casing reversely (4) and use the steel bar (5) to press the canvas casing
tightly onto the counter flange of the steel-plate ventilating duct (1). Use a hand-operated electric drill to
drill holes and fasten the parts by using tapping screws.
d)
Use the tin foil to seal the joints and check the joints' reliability.
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...