GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
123
system high-pressure value is
-15 to 5°C.
6
Opening
degree of
heating
electronic
expansion
valves
PLS
●During the cooling operation,
the heating electronic expansion
valves always remain at 480
PLS.
●During the heating operation,
the adjustable electronic
expansion valves change
between 120 and 480 PLS.
7
Operation
frequency of
inverter
compressor
Hz
●The operation frequency of
inverter compressor 1 changes
between 20 and 95 Hz.
●The operation frequency of
inverter compressor 2 changes
between 30 and 100 Hz.
8
Current of
inverter
compressor
A
●According to different oper
ation
frequencies and loads, the
current of inverter compressor 1
changes between 7 and 25 A.
The current of inverter
compressor 2 changes between 7
and 20 A.
9
IPM module
temperature of
inverter
compressor
°C
●When the environment
temperature is lower than 35°C,
the temperature of the IPM
module is lower than 80°C. The
highest temperature is not higher
than 95°C.
10
Driver bus line
voltage of
inverter
compressor
V
●The normal bus line voltage is
1.414 times larger than the
power voltage. For example, if
the three-phase power voltage is
390 V, the bus line voltage after
current rectification is 390 V ×
1.414 = 551 V. It is normal if the
difference between the actual
test value and the calculation
value is within 15 V.
11
Operation
frequency of
fan
Hz
●With the adjustment of system
pressure, the fans run between 0
and 65 Hz.
12
Indoor unit
parameter
Environment
temperature of
IDU
°C
——
13
Inlet-tube
temperature of
indoor heat
exchanger
°C
●As the environment
temperature is different, the
inlet-tube temperature is 1-7°C
lower than the outlet-tube
temperature of the same IDU in
cooling mode.
●The inlet
-tube temperature is
10-20°C lower than the
outlet-tube temperature of the
same IDU in heating mode.
14
Outlet-tube
temperature of
indoor heat
exchanger
°C
15
Opening
degree of
PLS
The opening degree
automatically changes between 0
Summary of Contents for GMV-224WM/B-X
Page 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Page 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Page 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Page 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Page 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Page 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Page 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Page 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Page 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Page 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Page 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Page 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Page 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Page 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Page 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Page 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Page 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Page 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Page 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Page 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Page 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Page 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Page 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Page 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...