Annex
English, Revision 09, Date: 13.12.2016
58
D.8
Restore Default Parameter
By writing the signature ’load’ in ASCII Code (hex-Code: 0x64616F6C) onto subindex
1, 2 or 3, the corresponding default parameters are loaded. A reset should be carried
out afterwards.
With ’Restore All’, the Node ID is also set to 1 and the baud rate to 125 Kbaud.
D.9
Producer Heartbeat Time
With 0 this function is deactivated.
Index
Sub Index
Name
Type
Attr.
Map
Default
Description
0x1011
00
Restore
Parameter
Unsigned 8
RO
No
0x03
Number of sub-
indexes
01
Restore All
Parameter
Unsigned 32
RW
No
0x00000001
Restore All is
possible
02
Restore Com.
Parameter
Unsigned 32
RW
No
0x00000001
Restore Com-
munication is
possible
03
Restore
Manufacture
Parameter
Unsigned 32
RW
No
0x00000001
Restore Manu-
facture is pos-
sible
Table 33
CANopen® Directory: Restore Default Parameter
Index
Sub Index
Name
Type
Attr.
Map
Default
Description
0x1017
00
Producer Heart-
beat Time
Unsigned 16
RW
No
1000
Heartbeat time in
ms (approx.)
Table 34
CANopen® Directory: Producer Heartbeat Time