3.13 EN-##
Ethernet
The parameters in this group are common for Ethernet IP
and Modbus TCP.
EN-00 IP Address Assignment
Option:
Function:
Selects the IP Address assignment method.
[0]
*
Manual IP-address can be set in
EN-01 IP Address
IP
Address.
[1]
DHCP
IP-address is assigned via DHCP server.
[2]
BOOTP
IP-address is assigned via BOOTP server.
EN-01 IP Address
Range:
Function:
[000.000.000.000 -
255.255.255.255]
Configure the IP address of the
option. Read-only if
EN-00 IP Address
Assignment
set to DHCP or BOOTP.
EN-02 Subnet Mask
Range:
Function:
[000.000.000.000 -
255.255.255.255]
Configure the IP subnet mask of the
option. Read-only if
EN-00 IP Address
Assignment
set to DHCP or BOOTP.
EN-03 Default Gateway
Range:
Function:
[000.000.000.000 –
255.255.255.255]
Configure the IP default gateway of
the option. Read-only if
EN-00 IP
Address Assignment
set to DHCP or
BOOTP.
EN-04 DHCP Server
Range:
Function:
[000.000.000.000 –
255.255.255.255]
Read only. Displays the IP address
of the found DHCP or BOOTP
server.
NOTE
A power-cycle is necessary after setting the IP parameters
manually.
EN-05 Lease Expires
Range:
Function:
0
*
[0 - 0] Read only. Displays the lease-time left for the
current DHCP-assigned IP address.
EN-06 Name Servers
Range:
Function:
0
*
[0 - 2147483647] IP addresses of Domain Name Servers.
Can be automatically assigned when
using DHCP.
EN-07 Domain Name
Range:
Function:
0 [0 - 2147483647] Domain name of the attached network.
Can be automatically assigned when using
DHCP network.
EN-08 Host Name
Range:
Function:
Blank
[0-19 characters]
Logical (given) name of option.
EN-09 Physical Address
Range:
Function:
0
*
[0 - 0] Read only. Displays the Physical (MAC) address of
the option.
EN-1# Ethernet Link parameters
Option:
Function:
Applies for whole parameter group.
[0]
Port 1
Index [0] goes for Port 1.
[1]
Port 2
Index [1] goes for Port 2.
EN-10 Link Status
Option:
Function:
Read only. Displays the link status of the Ethernet
ports.
[0]
*
No Link
[1]
Link
EN-11 Link Duration
Range:
Function:
0
*
[0 - 0] Read only. Displays the duration of the present link
on each port in dd:hh:mm:ss.
EN-12 Auto Negotiation
Option: Function:
Configures Auto Negotiation of Ethernet link
parameters, for each port: ON or OFF.
[0]
Off
Link Speed
and
Link Duplex
can be configured in
EN-13 Link Speed
and
[1]
On
EN-13 Link Speed
Option:
Function:
Forces the link speed for each port in 10 or 100
Mbps. If
EN-12 Auto Negotiation
is set to: [ON],
this parameter is read only and displays the
actual link speed. “None” is displayed if no link
is present.
[0]
*
None
[1]
10 Mbps
[2]
100 Mbps
Parameter Descriptions
AF-650 GP Programming Guide
102
DET-618C
3
3