2.1.7 Initial Commissioning
The easiest way of carrying out the initial commissioning is by pressing [Quick Menu] and following the quick set-up
procedure (read
from left to right). The example applies to open loop applications.
Press
Quick Start
Set language
K-02 Motor Speed Unit
Set motor speed in Hz or RPM
Set Motor nameplate power
Set Nameplate voltage
Set Nameplate frequency
Set Nameplate current
Set Nameplate speed in RPM
Set reference source
F-02 Operation Method
Select which reference site to activate
Set the accel time with reference to synchronous motor
speed, n
s
Set the decel time time with reference to synchronous
motor speed, n
s
Set motor thermal protection
F-15 Motor Speed High Limit [Hz]
or
F-17 Motor Speed High Limit [RPM]
Set motor speed high limit in Hz or RPM
F-16 Motor Speed Low Limit [Hz]
F-18 Motor Speed Low Limit [RPM]
Set motor speed low limit in Hz or RPM
Set allowed rotation direction
Set desired auto tune function. Enable complete auto
tune is recommended
Table 2.3
How to Program
AF-650 GP Programming Guide
DET-618C
19