3.9.5 SP-5# Environment
Parameters to enable/disable the optional factory installed
A1/B1 RFI Filter, and Fan Monitor and to configure an
output filter if installed.
SP-50 RFI Filter
Option:
Function:
[0]
Off
Select
[0] Off
if the frequency converter is fed by an
isolated mains source (IT mains).
If a filter is used, select
[0] Off
during charging to
prevent a high leakage current making the RCD
switch.
In this mode, the internal RFI filter capacitors between
chassis and the mains RFI filter circuit are cut-out to
reduce the ground capacity currents.
[1]
*
On
Select
[1] On
to ensure that the frequency converter
complies with EMC standards.
13
0BB9
08.1
0
Illustration 3.40 RFI Filter
SP-51 DC Link Compensation
Option:
Function:
The rectified AC-DC voltage at the frequency
converter's DC link is associated with voltage ripples.
These ripples can increase in magnitude with
increased load. These ripples are undesirable because
they can generate current and torque ripples. A
compensation method is used to reduce these voltage
ripples at DC link. In general, DC link compensation is
recommended for most applications, but care must be
taken when operating in field weakening as it can
generate speed oscillations at the motor shaft. In field
weakening, it is recommended to turn DC link
compensation off.
[0]
*
Off
Select
[0] Off
to disable DC Link Compensation. this
disables compensation for ripple in the DC bus and
may be set when harmonic filters are used with the
drive.
[1]
On
Select
[1] On
to enable DC Link Compensation. This
function compensates for lower or higher DC bus
voltages to recreate a more perfect sine wave. May
overcompensate when harmonic filters are used.
SP-52 Fan Operation
Select minimum speed of the main fan.
Option:
Function:
[0]
*
Auto
Select
[0] Auto
to run fan only when internal
temperature in frequency converter is in range
35
°
C to approx. 55
°
C.
Fan will run at low speed below 35
°
C, and at
full speed at approx. 55
°
C.
[1]
On 50%
The fan will always run at 50% speed or above.
The fan will run at 50% speed at 35
°
C, and at
full speed at approx. 55
°
C.
[2]
On 75%
The fan will always run at 75% speed or above.
The fan will run at 75% speed at 35
°
C, and at
full speed at approx. 55
°
C.
[3]
On 100% The fan will run at 100% speed always.
[4]
Auto
(Low
temp
env.)
This selection is the same as
[0] Auto
but with
special considerations around and below 0
°
C. In
selection
[0] Auto
there is a risk that the fan will
start running around 0
°
C as the frequency
converter will fear a sensor fault and thus
protect the frequency converter while reporting
warning 66 "Heatsink Temperature Low".
Selection
[4] Auto (Low temp env.)
can be used in
very cold environments and prevent the
negative effects of this further cooling and avoid
warning 66.
SP-53 Fan Monitor
Option:
Function:
Select which reaction the frequency converter
should take in case a fan fault is detected.
[0]
Disabled
[1]
*
Warning
[2]
Trip
SP-55 Output Filter
Option:
Function:
NOTE
This parameter cannot be adjusted while
motor is running.
Select if a Sine-Wave output filter connected.
[0]
*
No
Filter
This is the default setting and should be used with
dU/dt filters or high-frequency common-mode (HF-
CM) filters.
[1]
Sine-
Wave
Filter
This setting is only for backwards compatibility. It
enables operation with FLUX control principle
SP-57 Inductance Output Filter
are
programmed with the output filter capacitance
and inductance. It DOES NOT limit the range of
the switching frequency.
Parameter Descriptions
AF-650 GP Programming Guide
82
DET-618C
3