K-38 Display Text 2
Range:
Function:
0
*
[0 - 0] Enter a text which can be viewed in the graphical
display by selecting
[38] Display Text 2
in
K-20 Display Line 1.1 Small
,
K-21 Display Line 1.2
Small
,
K-22 Display Line 1.3 Small
,
K-23 Display Line 2
Large
or
K-24 Display Line 3 Large
.
K-39 Display Text 3
Range:
Function:
0
*
[0 - 0] Enter a text which can be viewed in the graphical
display by selecting
[39] Display Text 3
in
K-20 Display
Line 1.1 Small
,
K-21 Display Line 1.2 Small
,
K-22 Display Line 1.3 Small
,
K-23 Display Line 2 Large
or
K-24 Display Line 3 Large
.
3.2.5 K-4# Keypad Buttons
Parameters for configuring the graphical keypad Hand, Off,
Auto, & Reset keys.
K-40 [Hand] Button on Keypad
Option:
Function:
[0]
Disabled
Key disabled avoids accidental usage
of the key.
[1]
*
Enabled
[Hand ] key enabled
[2]
Password Protection
Avoid unauthorized start in Hand
is included in the Quick Start
Menu, then define the password in
K-65 Quick Menu Password
. Otherwise
define the password in
[3]
Enabled without
OFF
[4]
Password without
OFF
[5]
Enabled with OFF
[6]
Password with OFF
K-41 [Off] Button on Keypad
Option:
Function:
[0]
Disabled
Avoids accidental stop of the
frequency converter.
[1]
*
Enabled
[Off] Key enabled
[2]
Password Protection
is
included in the Quick Menu, then
define the password in
[3]
Hand Off/On
[4]
Hand Off/On w. Passw.
[7]
Enabled without OFF
K-41 [Off] Button on Keypad
Option:
Function:
[8]
Password without OFF
[9]
Enabled, ref = 0
K-42 [Auto] Button on Keypad
Option:
Function:
[0]
Disabled
Avoid accidental start of the
frequency converter in Auto mode.
[1]
*
Enabled
[Auto] Key enabled
[2]
Password Protection
Avoids unauthorised start in Auto
mode. If
is included in the Quick
Menu, then define the password in
[3]
Hand Off/On
[4]
Hand Off/On w. Passw.
[7]
Enabled without OFF
[8]
Password without OFF
[9]
Enabled, ref = 0
K-43 [Reset] Button on Keypad
Option:
Function:
[0]
Disabled
No effect when [Reset] is pressed.
Avoids accidental alarm reset.
[1]
*
Enabled
[Reset] Key enabled
[2]
Password
Protection
Avoids unauthorised resetting. If
is
included in the Quick Menu, then
define the password in
.
[3]
Hand Off/On
[4]
Hand Off/On w.
Passw.
[7]
Enabled without
OFF
Resets the frequency converter
without setting it in
Off
mode.
[8]
Password without
OFF
Resets the frequency converter
without setting it in
Off
mode. A
password is required when pressing
[Reset] (see [2]).
[9]
Enabled, ref = 0
3.2.6 K-5# Copy/Save
Copy parameter settings between set-ups and to/from the
keypad.
K-50 Keypad Copy
Option:
Function:
NOTE
This parameter cannot be adjusted
while the motor is running.
Parameter Descriptions
AF-650 GP Programming Guide
30
DET-618C
3
3