3.4 E-## Digital In/Out
Parameter group related to the Digital Inputs/Outputs, additional accel/decel ramps, pulse inputs/outputs, and encoder
input.
3.4.1 E-0# Digital Inputs
Parameters to configure the Digital Inputs/Outputs and Safe Stop functions.
Parameters for configuring the input functions for the input terminals.
The digital inputs are used for selecting various functions in the frequency converter. All digital inputs can be set to the
following functions:
Digital input function
Select
Terminal
No operation
[0]
All *term 27, 32, 33
Reset
[1]
All
Coast inverse
[2]
All
Coast and reset inverse
[3]
All
Quick stop inverse
[4]
All
DC-brake inverse
[5]
All
Stop inverse
[6]
All
Start
[8]
All *term 18
Latched start
[9]
All
Reversing
[10]
All *term 19
Start reversing
[11]
All
Enable start forward
[12]
All
Enable start reverse
[13]
All
Jog
[14]
All *term 29
Preset reference on
[15]
All
Preset ref bit 0
[16]
All
Preset ref bit 1
[17]
All
Preset ref bit 2
[18]
All
Freeze reference
[19]
All
Freeze output
[20]
All
Speed up
[21]
All
Speed down
[22]
All
Set-up select bit 0
[23]
All
Set-up select bit 1
[24]
All
Precise stop inverse
[26]
18, 19
Precises start, stop
[27]
18, 19
Catch up
[28]
All
Slow down
[29]
All
Counter input
[30]
29, 33
Pulse input
[32]
29, 33
Ramp bit 0
[34]
All
Ramp bit 1
[35]
All
Mains failure inverse
[36]
All
Latched precise start
[40]
18, 19
Latched precise stop inverse
[41]
18, 19
DigiPot Increase
[55]
All
DigiPot Decrease
[56]
All
DigiPot Clear
[57]
All
Counter A (up)
[60]
29, 33
Counter A (down)
[61]
29, 33
Reset Counter A
[62]
All
Parameter Descriptions
AF-650 GP Programming Guide
42
DET-618C
3
3